Omron relays. General Purpose Relays. G2AK

Latching Relay
G2AK

Magnetic Latching Version of G2A Ideal for Sequence Control

Contact form Classification Plug-in terminals PCB terminals
DPDT Standard model G2AK-232A G2AK-2321P
Arc barrier equipped model G2AK-232AY ---
Fully sealed model G2AK-234A ---
Note: 1. When placing your order, add the coil voltage rating to the model number as shown below.
G2AK Lineup 2
Note: 2. The applicable rated voltage range can be increased by connecting an external resistor. Refer to Specifications
for details.

Arc barrier equipped model

The arc barrier equipped model is a relay designed to prevent arc short-circuiting between phases and can be used in a circuit which has potential difference between phases. The switching power of such a circuit with potential difference must be limited to less than 1/2 the rated load when using this Relay.

Fully sealed model

The fully sealed model is a relay in a gas-tight plastic enclosure and thus exhibits stable performance in an adverse atmosphere of harmful gas, moisture, or powdery dust.

Accessories (Order Separately)

Sockets

Item DIN Track-mounting Socket Back-connecting Relay
Screw terminals Solder terminals Wire-wrap terminals PCB terminals
Without Hold-down Clip PYF14A(-E)
PYF14A-TU
PYF14T
PY14
PY14-3
PY14QN(2) PY14-0 PY14-02
With Hold-down Clip --- PY14-Y2 PY14QN-Y2 --- ---
Note: See the G2AK Datasheet for detailed information on the Relay Hold-down Clips and Socket Mounting Plates.

Coil Ratings

Rated
voltage
Set coil Reset coil Set
voltage
Reset
voltage
Max.
voltage
Power
consumption
Rated current Coil re-
sistance
Rated current Coil re-
sistance
Set
coil
Reset
coil
50 Hz 60 Hz 50 Hz 60 Hz
12 VAC 162 mA 158 mA 28 Ω 40 mA 39 mA 125 Ω 80%
max. of
rated
voltage
80%
max. of
rated
voltage
110%
of
rated
voltage
Approx.
1.6 to
2.0 VA
Approx.
0.5 to
1.2 VA
24 VAC 66 mA 64 mA 145 Ω 22.6 mA 22 mA 460 Ω
50 VAC 34 mA 33 mA 590 Ω 11.3 mA 11 mA 1,900 Ω
100 VAC 19 mA 18.5 mA 2,150 Ω 12.3 mA 12 mA 3,600 Ω
6 VDC 360 mA 14 Ω 160 mA 32 Ω Approx.
2.0 to
2.2 W
Approx.
1.0 to
1.2 W
12 VDC 170 mA 65 Ω 85 mA 125 Ω
24 VDC 85 mA 270 Ω 50 mA 460 Ω
48 VDC 44 mA 1,050 Ω 24 mA 1,900 Ω
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%, –20%
for AC rated current and ±15% for DC coil resistance.
2. The AC coil resistance values are for reference only.
3. Performance characteristics data are measured at a coil temperature of 23°C.
4. The rated current of the AC operating coil is half-wave rectified current and is measured with a DC ammeter.
5. The peak reverse-breakdown voltage of the built-in diode is 1,000V.
6. The set coil of the Relay rated at 6 VDC is of the 5-minute rating. However, when it is used by connecting a diode
is series, it can be of the continuous rating.
7. By connecting an external resistor to each of the set and reset coils as shown in the table below, the rated current
of the Relay can be increased.
8. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.

Rated voltage
Connected coil voltage External resistor
Set coil Reset coil
Resistance Capacity Resistance Capacity
110 VAC 100 VAC 0.27 kΩ 0.5 W min. 0.39 kΩ 1/4 W min.
200 VAC 100 VAC 2.7 kΩ 5 W min. 8.2 kΩ 3 W min.
220 VAC 100 VAC 3.3 kΩ 6 W min. 9.1 kΩ 3 W min.
100 VDC 48 VDC 1.1 kΩ 10 W min. 2.0 kΩ 6 W min.
Note: Use a resistor having the above resistance value with tolerances of ±10% for external connection.

Method of Connection

G2AK Specifications 5
  • Reset side
    DC coil: Connect terminal No. 13 to terminal No. 9 or No. 13 to No. 5.
    AC coil: Connect terminal No. 13 to terminal No. 5.
  • Set side
    DC coil: Connect terminal No. 14 to terminal No. 12 or No. 14 to No. 8.
    AC coil: Connect terminal No. 14 to terminal No. 8.

Contact Ratings

Load Resistive load (cosφ = 1) Inductive load (cosφ = 0.4) (L/R = 7 ms)
Contact type Crossbar bifurcated
Contact material Movable: Au-clad AgPd
Fixed: AgPd
Rated load 0.3 A at 110 VAC
0.5 A at 24 VDC
0.2 A at 110 VAC
0.3 A at 24 VDC
Rated carry current 3 A
Max. switching voltage 250 VAC, 125 VDC

Characteristics

Contact resistance
(see note 2)
100 mΩ max.
Set time
(see note 3)
AC: 25 ms max.; DC: 15 ms max.
Reset time
(see note 3)
AC: 25 ms max.; DC: 15 ms max.
Min. pulse width AC: 50 ms; DC: 30 ms
Max. operating frequency Mechanical: 18,000 operations/hour
Electrical: 1,800 operations/hour (under rated load)
Insulation resistance
(see note 4)
100 MΩ min. (at 500 VDC)
Dielectric strength 1,500 VAC, 50/60 Hz for 1 minute between coil and contact (700 VAC between contacts
of same pole) (1,000 VAC between set and reset coils)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
(for contact malfunction);
3.0-mm double amplitude (for armature malfunction)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 100 m/s2, 300 m/s2
Endurance Mechanical: 100,000,000 operations min. (at operating frequency of 18,000 operations/
hour)
Electrical: 5,000,000 operations min. (under rated load and at operating frequency of 1,800
operations/hour) (see note 5)
Error rate (level P)
(Reference value)
(see note 6)
1 mA at 100 mVDC
Ambient temperature Operating: -10°C to 40°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 38 g
Note: 1. The data shown above are initial values.
2. The contact resistance was measured with 0.1 A at 5 VDC using the fall-of-potential method.
3. The set or reset time was measured with the rated voltage imposed with any contact bounce ignored at an
ambient temperature of 23°C.
4. The insulation resistance was measured with a 500-VDC megger applied to the same places as those used
for checking the dielectric strength.
5. The electrical endurance was measured at an ambient temperature of 23°C.
6. This value was measured at a switching frequency of 60 operations per minute.

G2AK-232

G2AK Dimensions 1

Arc Barrier Equipped Models

with Plug-in Terminals
G2AK-232A(Y)

G2AK Dimensions 3

with PCB Terminals
G2AK-2321P(Y)

G2AK Dimensions 4

Fully Sealed Models

with Plug-in Terminals
G2AK-234A

G2AK Dimensions 6

with PCB Terminals
G2AK-2341P

G2AK Dimensions 7

Mounting Holes on
PCB (Bottom View)

Note: Dimensional tolerances are ±0.1 mm
G2AK Dimensions 8

Terminal Arrangement/Internal Connections (Bottom View)

G2AK Dimensions 9
Note: Terminals (Nos. 12 and 9) are pulled from the respective junctions between the diode and set coil and between the
diode and reset coil. Use these terminals through external connection for selective use or non-use of the diodes as
well as for surge prevention.