• Russian
  • Spain
  • Italy
  • France
  • Deutsch
  • English

Browse All Products

Omron relays. Solid State Relays. G3NA

Solid State Relays
G3NA

Wide Lineup of General-purpose Solid State Relays with Applicable Loads of 5 to 90 A

Isolation Zero cross
function
Indicator Applicable
output load *1
Rated input
voltage
Model
Phototriac
Coupler
Yes Yes
(Yellow)
5 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-205B DC5-24
Photocoupler 100 to 120 VAC G3NA-205B AC100-120
200 to 240 VAC G3NA-205B AC200-240
Phototriac
Coupler
10 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-210B DC5-24
Photocoupler 100 to 120 VAC G3NA-210B AC100-120
200 to 240 VAC G3NA-210B AC200-240
Phototriac
Coupler
20 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-220B DC5-24
Photocoupler 100 to 120 VAC G3NA-220B AC100-120
200 to 240 VAC G3NA-220B AC200-240
Phototriac
Coupler
40 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-240B DC5-24
Photocoupler 100 to 120 VAC G3NA-240B AC100-120
200 to 240 VAC G3NA-240B AC200-240
Phototriac
Coupler
75 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-275B-UTU-2 DC5-24
Photocoupler 100 to 120 VAC G3NA-275B-UTU-2 AC100-240
Phototriac
Coupler
90 A at 24 to
240 VAC *2
5 to 24 VDC G3NA-290B-UTU-2 DC5-24
Photocoupler 100 to 240 VAC G3NA-290B-UTU-2 AC100-240
Yes 10 A at 200 to
480 VAC
5 to 24 VDC G3NA-410B DC5-24
100 to 240 VAC G3NA-410B AC100-240
20 A at 200 to
480 VAC
5 to 24 VDC G3NA-420B DC5-24
100 to 240 VAC G3NA-420B AC100-240
40 A at 200 to
480 VAC
5 to 24 VDC G3NA-440B-2 DC5-24
100 to 240 VAC G3NA-440B-2 AC100-240
50 A at 200 to
480 VAC *2
5 to 24 VDC G3NA-450B-2 DC5-24
75 A at 200 to
480 VAC *2
5 to 24 VDC G3NA-475B-UTU-2 DC5-24
100 to 240 VAC G3NA-475B-UTU-2 AC100-240
90 A at 200 to
480 VAC *2
5 to 24 VDC G3NA-490B-UTU-2 DC5-24
100 to 240 VAC G3NA-490B-UTU-2 AC100-240
--- 10 A at 5 to
200 VDC
5 to 24 VDC G3NA-D210B DC5-24
100 to 240 VAC G3NA-D210B AC100-240
Note: The standard models are certified by UL and CSA.
To order a TÜV-certified model for G3NA-205BN/210B/220B/240B/D210B, add “-UTU” to the model number.
*1. The applicable load is the value for when the SSR is used with silicon grease applied to the specified heat sink. The
applicable load depends on the ambient temperature. Refer to Load Current vs. Ambient Temperature in
Engineering Data on Catalog.
*2. Loss time increases under 75 VAC. (Refer to Catalog.) Confirm operation with the actual load.

Accessories (Order Separately)

One-touch Mounting Plates

Model
R99-12 FOR G3NA

Mounting Bracket

Model Applicable SSR
R99-11 G3NA-240B, G3NA-440B(-2)

Heat Sinks

Slim Models Enabling DIN-track Mounting

Model Applicable SSR
Y92B-N50 G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B, G3NA-210T(L)
Y92B-N100 G3NA-220B, G3NA-420B, G3NA-220T(L)
Y92B-N150 G3NA-240B, G3NA-440B-2
Y92B-P250 G3NA-450B-2
Y92B-P250NF * G3NA-275B-UTU-2, G3NA-290B-UTU-2, G3NA-475B-UTU-2, G3NA-490B-UTU-2
* The Y92B-P250NF is scheduled for release on May 1, 2004.

Low-cost Models

Model Applicable SSR
Y92B-A100 G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B
Y92B-A150N G3NA-240B-2, G3NA-440B-2
Y92B-A250 G3NA-440B-2

Input (at an Ambient Temperature of 25°C)

Model Rated voltage Operating
voltage
Impedance *1 Voltage level
Must operate
voltage
Must release
voltage
G3NA-2[][]B 5 to 24 VDC 4 to 32 VDC 7 mA max. *2 4 VDC max. 1 VDC min.
100 to 120 VAC 75 to 132 VAC 36 kΩ±20% *4 75 VAC max. *3 20 VAC min. *3
200 to 240 VAC 150 to 264 VAC 72 kΩ±20% 150 VAC max. *3 40 VAC min. *3 *5
G3NA-4[][]B
G3NA-D210B
5 to 24 VDC 4 to 32 VDC 5 mA max. *2 4 VDC max. 1 VDC min.
100 to 240 VAC 75 to 264 VAC 72 kΩ±20% 75 VAC max. 20 VAC min.
G3NA-275B-UTU-2
G3NA-290B-UTU-2
5 to 24 VDC 4 to 32 VDC 15 mA max. 4 VDC max. 1 VDC min.
100 to 240 VAC 75 to 264 VAC 72 kΩ±20% 75 VAC max. 20 VAC min.
G3NA-475B-UTU-2
G3NA-490B-UTU-2
5 to 24 VDC 4 to 32 VDC 7 mA max. 4 VDC max. 1 VDC min.
100 to 240 VAC 75 to 264 VAC 72 kΩ±20% 75 VAC max. 20 VAC min.
*1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model
rated at 100 to 120 VAC, the input impedance is measured at 120 VAC).
*2. With constant current input circuit system. The impedance for the G3NA-2[][]B-UTU is 15 mA max.
*3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data on
Catalog for further details.
*4. The G3NA-240B(-UTU) is 72kΩ±20%.
*5. The G3NA-240B(-UTU) is 20 VAC min.

Output

Model Rated
load
voltage
Load
voltage
range
Load current *1 Inrush current VDRM,
VCEO
(reference
value)
With heat sink *2 Without heat
sink
G3NA-205B 24 to
240 VAC
19 to
264 VAC
0.1 to 5 A (at 40°C) 0.1 to 3 A (at 40°C) 60 A (60 Hz, 1 cycle) 600 V
(VDRM)
G3NA-210B 0.1 to 10 A (at 40°C) 0.1 to 4 A (at 40°C) 150 A (60 Hz, 1 cycle)
G3NA-220B 0.1 to 20 A (at 40°C) 0.1 to 4 A (at 40°C) 220 A (60 Hz, 1 cycle)
G3NA-240B 0.1 to 40 A (at 40°C) 0.1 to 6 A (at 40°C) 440 A (60 Hz, 1 cycle)
G3NA-410B 200 to
480 VAC
180 to
528 VAC
0.2 to 10 A (at 40°C) 0.2 to 4 A (at 40°C) 150 A (60 Hz, 1 cycle) 1,200 V
(VDRM)
G3NA-420B 0.2 to 20 A (at 40°C) 0.2 to 4 A (at 40°C) 220 A (60 Hz, 1 cycle)
G3NA-440B-2 0.2 to 40 A (at 40°C) 0.2 to 6 A (at 40°C) 440 A (60 Hz, 1 cycle)
G3NA-D210B 5 to
200 VDC
4 to
220 VDC
0.1 to 10 A (at 40°C) 0.1 to 4 A (at 40°C) 20 A (10 ms) 400 V
(VCEO)
G3NA-275B-UTU-2 24 to
240 VAC
19 to
264 VAC
1 to 75 A (at 40°C) 1 to 7 A (at 40°C) 800 A (60 Hz, 1 cycle) 600 V
(VDRM)
G3NA-290B-UTU-2 1 to 90 A (at 40°C) 1 to 7 A (at 40°C) 1,000 A (60 Hz, 1 cycle)
G3NA-475B-UTU-2 200 to
480 VAC
180 to
528 VAC
1 to 75 A (at 40°C) 1 to 7 A (at 40°C) 800 A (60 Hz, 1 cycle) 1,200 V
(VDRM)
G3NA-490B-UTU-2 1 to 90 A (at 40°C) 1 to 7 A (at 40°C) 1,000 A (60 Hz, 1 cycle)
*1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature
under Engineering Data on Catalog.
*2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.

Characteristics

Item G3NA-205B
G3NA-210B
G3NA-220B
G3NA-
240B
G3NA-410B
G3NA-420B
G3NA-440B-2
G3NA-450B-2
G3NA-
D210B
G3NA-275B-
UTU-2
G3NA-290B-
UTU-2
G3NA-475B-
UTU-2
G3NA-490B-
UTU-2
Operate
time
1/2 of load power source cycle + 1 ms max.
(DC input)
3/2 of load power source cycle + 1 ms max.
(AC input)
1 ms max.
(DC input)
30 ms max.
(AC input)
1/2 of load power source cycle +
1 ms max. (DC input)
3/2 of load power source cycle +
1 ms max. (AC input)
Release
time
1/2 of load power source cycle + 1 ms max.
(DC input)
3/2 of load power source cycle + 1 ms max.
(AC input)
5 ms max.
(DC input)
30 ms max.
(AC input)
1/2 of load power source cycle +
1 ms max. (DC input)
3/2 of load power source cycle +
1 ms max. (AC input)
Output ON
voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max. 1.5 V max. 1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage
current
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
10 mA max.
(at 200 VAC)
20 mA max.
(at 400 VAC)
5 mA max.
(at 200
VDC)
5 mA max.
(at 100 VAC)
10 mA max.
(at 200 VAC)
10 mA max.
(at 200 VAC)
20 mA max.
(at 400 VAC)
Insulation
resistance
100 MΩ min. (at 500 VDC)
Dielectric
strength
2,500 VAC, 50/60 Hz for 1 min 4,000 VAC, 50/60 Hz for 1 min
Vibration
resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock
resistance
Destruction: 1,000 m/s2
Ambient
temperature
Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation)
Ambient
humidity
Operating: 45% to 85%
Weight Approx. 60 g Approx. 70 g Approx. 80 g Approx. 70 g Approx. 120 g
G3NA-D210B, G3NA-205B, G3NA-210B, G3NA-220B
G3NA Dimensions 2
Note: The load can be connected to either the positive or negative side.
G3NA-240B, G3NA-275B-UTU-2, G3NA-290B-UTU-2,
G3NA-440B-2, G3NA-475B-UTU-2, G3NA-490B-UTU-2

G3NA Dimensions 4
G3NA-410B, G3NA-420B
G3NA Dimensions 5
G3NA Dimensions 6

Options (Order Separately)

One-touch Mounting Plate

The One-touch Mounting Plate is used to mount the GN3A to a DIN Track.

R99-12 FOR G3NA (for the G3NA and G3NE)

G3NA Dimensions 9

Mounting Bracket

R99-11 (for the G3NA-240B, G3NA-440B-2)

Use Mounting Bracket R99-11 so that the G3NA-240B/-440B can be mounted with the same pitch as that of the G3N-240B.
G3NA Dimensions 11

Heat Sinks

Y92B-N50 Heat Sink (for the G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B, G3NE-210T(L))

For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).
For mounting method, refer to "Precautions for Correct Use".
G3NA Dimensions 13
Weight: approx. 200 g

Y92B-N100 Heat Sink (for the G3NA-220B, G3NA-420B, G3NE-220T(L))

For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).
For mounting method, refer to "Precautions for Correct Use".
G3NA Dimensions 15
Weight: approx. 400 g

Y92B-N150 Heat Sink (for the G3NA-240B, G3NA-440B-2)

For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).
For mounting method, refer to "Precautions for Correct Use".
G3NA Dimensions 17
Weight: approx. 560 g

Y92B-P250NF Heat Sink (for the G3NA-275B-UTU(-2), G3NA-475B-UTU(-2), G3NA-290B-UTU(-2), G3NA-490B-UTU(-2))

For mounting method, refer to "Precautions for Correct Use".
G3NA Dimensions 19
Weight: approx. 2.5 kg

Y92B-P250

G3NA Dimensions 21

Y92B-A100 Heat Sink
(for the G3NA-205B, G3NA-210B, G3NA-220B, G3NA-410B, G3NA-420B, G3NA-D210B)

G3NA Dimensions 22
Weight: approx. 210 g

Y92B-A150N Heat Sink
(for the G3NA-240B, G3NA-440B-2)

G3NA Dimensions 23
Weight: approx. 310 g

Y92B-A250 Heat Sink
(for the G3NA-440B-2)

G3NA Dimensions 24
Weight: approx. 510 g

Mounting Holes
Y92B-A100
Y92B-A150
Y92B-A250

G3NA Dimensions 25
For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).
For mounting method, refer to "Precautions for Correct Use".