Omron relays. Solid State Relays. G3NA
Solid State Relays
Wide Lineup of General-purpose Solid State Relays with Applicable Loads of 5 to 90 A
Isolation | Zero cross function |
Indicator | Applicable output load *1 |
Rated input voltage |
Model |
Phototriac Coupler |
Yes | Yes (Yellow) |
5 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-205B DC5-24 |
Photocoupler | 100 to 120 VAC | G3NA-205B AC100-120 | |||
200 to 240 VAC | G3NA-205B AC200-240 | ||||
Phototriac Coupler |
10 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-210B DC5-24 | ||
Photocoupler | 100 to 120 VAC | G3NA-210B AC100-120 | |||
200 to 240 VAC | G3NA-210B AC200-240 | ||||
Phototriac Coupler |
20 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-220B DC5-24 | ||
Photocoupler | 100 to 120 VAC | G3NA-220B AC100-120 | |||
200 to 240 VAC | G3NA-220B AC200-240 | ||||
Phototriac Coupler |
40 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-240B DC5-24 | ||
Photocoupler | 100 to 120 VAC | G3NA-240B AC100-120 | |||
200 to 240 VAC | G3NA-240B AC200-240 | ||||
Phototriac Coupler |
75 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-275B-UTU-2 DC5-24 | ||
Photocoupler | 100 to 120 VAC | G3NA-275B-UTU-2 AC100-240 | |||
Phototriac Coupler |
90 A at 24 to 240 VAC *2 |
5 to 24 VDC | G3NA-290B-UTU-2 DC5-24 | ||
Photocoupler | 100 to 240 VAC | G3NA-290B-UTU-2 AC100-240 | |||
Yes | 10 A at 200 to 480 VAC |
5 to 24 VDC | G3NA-410B DC5-24 | ||
100 to 240 VAC | G3NA-410B AC100-240 | ||||
20 A at 200 to 480 VAC |
5 to 24 VDC | G3NA-420B DC5-24 | |||
100 to 240 VAC | G3NA-420B AC100-240 | ||||
40 A at 200 to 480 VAC |
5 to 24 VDC | G3NA-440B-2 DC5-24 | |||
100 to 240 VAC | G3NA-440B-2 AC100-240 | ||||
50 A at 200 to 480 VAC *2 |
5 to 24 VDC | G3NA-450B-2 DC5-24 | |||
75 A at 200 to 480 VAC *2 |
5 to 24 VDC | G3NA-475B-UTU-2 DC5-24 | |||
100 to 240 VAC | G3NA-475B-UTU-2 AC100-240 | ||||
90 A at 200 to 480 VAC *2 |
5 to 24 VDC | G3NA-490B-UTU-2 DC5-24 | |||
100 to 240 VAC | G3NA-490B-UTU-2 AC100-240 | ||||
--- | 10 A at 5 to 200 VDC |
5 to 24 VDC | G3NA-D210B DC5-24 | ||
100 to 240 VAC | G3NA-D210B AC100-240 |
To order a TÜV-certified model for G3NA-205BN/210B/220B/240B/D210B, add “-UTU” to the model number.
*1. The applicable load is the value for when the SSR is used with silicon grease applied to the specified heat sink. The
applicable load depends on the ambient temperature. Refer to Load Current vs. Ambient Temperature in
Engineering Data on Catalog.
*2. Loss time increases under 75 VAC. (Refer to Catalog.) Confirm operation with the actual load.
Accessories (Order Separately)
One-touch Mounting Plates
Model |
R99-12 FOR G3NA |
Mounting Bracket
Model | Applicable SSR |
R99-11 | G3NA-240B, G3NA-440B(-2) |
Heat Sinks
Slim Models Enabling DIN-track Mounting
Model | Applicable SSR |
Y92B-N50 | G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B, G3NA-210T(L) |
Y92B-N100 | G3NA-220B, G3NA-420B, G3NA-220T(L) |
Y92B-N150 | G3NA-240B, G3NA-440B-2 |
Y92B-P250 | G3NA-450B-2 |
Y92B-P250NF * | G3NA-275B-UTU-2, G3NA-290B-UTU-2, G3NA-475B-UTU-2, G3NA-490B-UTU-2 |
Low-cost Models
Model | Applicable SSR |
Y92B-A100 | G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B |
Y92B-A150N | G3NA-240B-2, G3NA-440B-2 |
Y92B-A250 | G3NA-440B-2 |
Input (at an Ambient Temperature of 25°C)
Model | Rated voltage | Operating voltage |
Impedance *1 | Voltage level | |
Must operate voltage |
Must release voltage |
||||
G3NA-2[][]B | 5 to 24 VDC | 4 to 32 VDC | 7 mA max. *2 | 4 VDC max. | 1 VDC min. |
100 to 120 VAC | 75 to 132 VAC | 36 kΩ±20% *4 | 75 VAC max. *3 | 20 VAC min. *3 | |
200 to 240 VAC | 150 to 264 VAC | 72 kΩ±20% | 150 VAC max. *3 | 40 VAC min. *3 *5 | |
G3NA-4[][]B G3NA-D210B |
5 to 24 VDC | 4 to 32 VDC | 5 mA max. *2 | 4 VDC max. | 1 VDC min. |
100 to 240 VAC | 75 to 264 VAC | 72 kΩ±20% | 75 VAC max. | 20 VAC min. | |
G3NA-275B-UTU-2 G3NA-290B-UTU-2 |
5 to 24 VDC | 4 to 32 VDC | 15 mA max. | 4 VDC max. | 1 VDC min. |
100 to 240 VAC | 75 to 264 VAC | 72 kΩ±20% | 75 VAC max. | 20 VAC min. | |
G3NA-475B-UTU-2 G3NA-490B-UTU-2 |
5 to 24 VDC | 4 to 32 VDC | 7 mA max. | 4 VDC max. | 1 VDC min. |
100 to 240 VAC | 75 to 264 VAC | 72 kΩ±20% | 75 VAC max. | 20 VAC min. |
rated at 100 to 120 VAC, the input impedance is measured at 120 VAC).
*2. With constant current input circuit system. The impedance for the G3NA-2[][]B-UTU is 15 mA max.
*3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data on
Catalog for further details.
*4. The G3NA-240B(-UTU) is 72kΩ±20%.
*5. The G3NA-240B(-UTU) is 20 VAC min.
Output
Model | Rated load voltage |
Load voltage range |
Load current *1 | Inrush current | VDRM, VCEO (reference value) |
|
With heat sink *2 | Without heat sink |
|||||
G3NA-205B | 24 to 240 VAC |
19 to 264 VAC |
0.1 to 5 A (at 40°C) | 0.1 to 3 A (at 40°C) | 60 A (60 Hz, 1 cycle) | 600 V (VDRM) |
G3NA-210B | 0.1 to 10 A (at 40°C) | 0.1 to 4 A (at 40°C) | 150 A (60 Hz, 1 cycle) | |||
G3NA-220B | 0.1 to 20 A (at 40°C) | 0.1 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-240B | 0.1 to 40 A (at 40°C) | 0.1 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-410B | 200 to 480 VAC |
180 to 528 VAC |
0.2 to 10 A (at 40°C) | 0.2 to 4 A (at 40°C) | 150 A (60 Hz, 1 cycle) | 1,200 V (VDRM) |
G3NA-420B | 0.2 to 20 A (at 40°C) | 0.2 to 4 A (at 40°C) | 220 A (60 Hz, 1 cycle) | |||
G3NA-440B-2 | 0.2 to 40 A (at 40°C) | 0.2 to 6 A (at 40°C) | 440 A (60 Hz, 1 cycle) | |||
G3NA-D210B | 5 to 200 VDC |
4 to 220 VDC |
0.1 to 10 A (at 40°C) | 0.1 to 4 A (at 40°C) | 20 A (10 ms) | 400 V (VCEO) |
G3NA-275B-UTU-2 | 24 to 240 VAC |
19 to 264 VAC |
1 to 75 A (at 40°C) | 1 to 7 A (at 40°C) | 800 A (60 Hz, 1 cycle) | 600 V (VDRM) |
G3NA-290B-UTU-2 | 1 to 90 A (at 40°C) | 1 to 7 A (at 40°C) | 1,000 A (60 Hz, 1 cycle) | |||
G3NA-475B-UTU-2 | 200 to 480 VAC |
180 to 528 VAC |
1 to 75 A (at 40°C) | 1 to 7 A (at 40°C) | 800 A (60 Hz, 1 cycle) | 1,200 V (VDRM) |
G3NA-490B-UTU-2 | 1 to 90 A (at 40°C) | 1 to 7 A (at 40°C) | 1,000 A (60 Hz, 1 cycle) |
under Engineering Data on Catalog.
*2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
Characteristics
Item | G3NA-205B G3NA-210B G3NA-220B |
G3NA- 240B |
G3NA-410B G3NA-420B G3NA-440B-2 G3NA-450B-2 |
G3NA- D210B |
G3NA-275B- UTU-2 G3NA-290B- UTU-2 |
G3NA-475B- UTU-2 G3NA-490B- UTU-2 |
Operate time |
1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) |
1 ms max. (DC input) 30 ms max. (AC input) |
1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) |
|||
Release time |
1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) |
5 ms max. (DC input) 30 ms max. (AC input) |
1/2 of load power source cycle + 1 ms max. (DC input) 3/2 of load power source cycle + 1 ms max. (AC input) |
|||
Output ON voltage drop |
1.6 V (RMS) max. | 1.8 V (RMS) max. | 1.5 V max. | 1.6 V (RMS) max. | 1.8 V (RMS) max. | |
Leakage current |
5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC) |
10 mA max. (at 200 VAC) 20 mA max. (at 400 VAC) |
5 mA max. (at 200 VDC) |
5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC) |
10 mA max. (at 200 VAC) 20 mA max. (at 400 VAC) |
|
Insulation resistance |
100 MΩ min. (at 500 VDC) | |||||
Dielectric strength |
2,500 VAC, 50/60 Hz for 1 min | 4,000 VAC, 50/60 Hz for 1 min | ||||
Vibration resistance |
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) | |||||
Shock resistance |
Destruction: 1,000 m/s2 | |||||
Ambient temperature |
Operating: -30°C to 80°C (with no icing or condensation) Storage: -30°C to 100°C (with no icing or condensation) |
|||||
Ambient humidity |
Operating: 45% to 85% | |||||
Weight | Approx. 60 g | Approx. 70 g | Approx. 80 g | Approx. 70 g | Approx. 120 g |

Note: The load can be connected to either the positive or negative side.
G3NA-240B, G3NA-275B-UTU-2, G3NA-290B-UTU-2,
G3NA-440B-2, G3NA-475B-UTU-2, G3NA-490B-UTU-2

G3NA-410B, G3NA-420B


Options (Order Separately)
One-touch Mounting Plate
R99-12 FOR G3NA (for the G3NA and G3NE)

Mounting Bracket
R99-11 (for the G3NA-240B, G3NA-440B-2)
Use Mounting Bracket R99-11 so that the G3NA-240B/-440B can be mounted with the same pitch as that of the G3N-240B.
Heat Sinks
Y92B-N50 Heat Sink (for the G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B, G3NE-210T(L))
For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).For mounting method, refer to "Precautions for Correct Use".

Weight: approx. 200 g
Y92B-N100 Heat Sink (for the G3NA-220B, G3NA-420B, G3NE-220T(L))
For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).For mounting method, refer to "Precautions for Correct Use".

Weight: approx. 400 g
Y92B-N150 Heat Sink (for the G3NA-240B, G3NA-440B-2)
For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).For mounting method, refer to "Precautions for Correct Use".

Weight: approx. 560 g
Y92B-P250NF Heat Sink (for the G3NA-275B-UTU(-2), G3NA-475B-UTU(-2), G3NA-290B-UTU(-2), G3NA-490B-UTU(-2))
For mounting method, refer to "Precautions for Correct Use".
Weight: approx. 2.5 kg
Y92B-P250

Y92B-A100 Heat Sink
(for the G3NA-205B, G3NA-210B, G3NA-220B, G3NA-410B, G3NA-420B, G3NA-D210B)

Weight: approx. 210 g
Y92B-A150N Heat Sink
(for the G3NA-240B, G3NA-440B-2)

Weight: approx. 310 g
Y92B-A250 Heat Sink
(for the G3NA-440B-2)

Weight: approx. 510 g
Mounting Holes
Y92B-A100
Y92B-A150
Y92B-A250

For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs).
For mounting method, refer to "Precautions for Correct Use".