Omron relays. Solid State Relays. G3TA

Solid State Relays
G3TA

I/O SSRs That Mount to OMRON's G7TC I/O Block

Input Modules

Isolation Indicator Logic level Rated input voltage Model
Supply voltage Supply current
Photocoupler Yes 4 to 32 VDC 25 mA 100 to 240 VAC G3TA-IAZR02S-US
5 to 24 VDC G3TA-IDZR02S-US
No 4 to 24 VDC G3TA-IDZR02SM-US
Note: When ordering, specify the rated input voltage.

Output Modules

Isolation Zero cross
function
Indicator Rated output load Rated input
voltage
Model
Phototriac Yes Yes 2 A at 100 to 240 VAC at
60 ° C
12 VDC G3TA-OA202SZ-US
24 VDC
No 12 VDC G3TA-OA202SL-US
24 VDC
Photocoupler --- 2 A at 5 to 48 VDC at 60 ° C 12 VDC G3TA-ODX02S-US
24 VDC
1 A at 48 to 200 VDC at 40 ° C 12 VDC G3TA-OD201S-US
24 VDC
Note: 1. For information on products that are certified for international standards, consult your OMRON sales
representatives.
(Models certified for UL and CSA standards have "-US" at the end of the model number.)
2. Input Modules are mainly suitable for signal input to PLCs. For load switching, consider using an Output Module.

I/O Indication

The modules are classified as Input Modules and Output Modules according to the main application of the Module.
I/O module classification and AC/DC use are indicated on the mark affixed to the top of the product.

Mark indication
Specification
AC IN Input module, AC input
DC IN Input module, DC input
AC OUT Output module, AC output
DC OUT Output module, DC output
G3TA Lineup 7

Accessories (Order Separately)

Connecting Socket

I/O classification Rated voltage Model
Input (NPN, - common) 12 VDC P7TF-IS16
24 VDC
100/110 VDC
100/110 VAC
200/220 VAC
Output (NPN, + common) 12 VDC P7TF-OS16
24 VDC
Output (PNP, - common) 12 VDC P7TF-OS16-1
24 VDC
Output (NPN, + common) 12 VDC P7TF-OS08
24 VDC
--- --- P7TF-05

Ratings (at an Ambient Temperature of 25°C)

Input Module

Input

Model Rated voltage Operating voltage Input
current
Voltage level
Must operate
voltage
Must release
voltage
G3TA-IAZR02S-US 100 to 240 VAC 80 to 264 VAC 5 mA max. 80 VAC max. 10 VAC min.
G3TA-IDZR02S-US 5 to 24 VDC 4 to 32 VDC 4 VDC max. 1 VDC min.
G3TA-IDZR02SM-US 4 to 24 VDC 3 to 32 VDC 3 VDC max.

Output

Model Logic level supply
voltage
Output breakdown
voltage
Output current Output current
(load current)
VCEO
(reference value)
G3TA-IAZR02S-US 4 to 32 VDC 32 VDC max. 25 mA max. 0.1 to 25 mA 80 V
G3TA-IDZR02S-US
G3TA-IDZR02SM-US

Output Module

Input

Model Rated
voltage
Operating voltage Input
impedance
Voltage level
Must operate voltage Must release
voltage
G3TA-OA202SZ-US 12 VDC 9.6 to 13.2 VDC 0.9 kΩ±20% 9.6 VDC max. 2 VDC min.
24 VDC 19.2 to 26.4 VDC 1.7 kΩ±20% 19.2 VDC max.
G3TA-OA202SL-US 12 VDC 9.6 to 13.2 VDC 0.9 kΩ±20% 9.6 VDC max.
24 VDC 19.2 to 26.4 VDC 1.7 kΩ±20% 19.2 VDC max.
G3TA-ODX02S-US 12 VDC 9.6 to 13.2 VDC 3.5 kΩ±20% 9.6 VDC max.
24 VDC 19.2 to 26.4 VDC 6.5 kΩ±20% 19.2 VDC max.
G3TA-OD201S-US 12 VDC 9.6 to 13.2 VDC 3.6 kΩ±20% 9.6 VDC max.
24 VDC 19.2 to 26.4 VDC 6.4 kΩ±20% 19.2 VDC max.

Output

Model Rated load
voltage
Load voltage
range
Load current
(See note.)
Inrush current VDRM, VCEO
(reference value)
G3TA-OA202SZ-US 100 to 240 VAC 75 to 264 VAC 0.05 to 2 A 30 A (60 Hz, 1 cycle) 600 (VDRM)
G3TA-OA202SL-US 100 to 240 VAC 75 to 264 VAC
G3TA-ODX02S-US 5 to 48 VDC 4 to 60 VDC 0.01 to 2 A 12 A (10 ms) 80 (VCEO)
G3TA-OD201S-US 48 to 200 VDC 40 to 200 VDC 0.01 to 1 A 6 A (10 ms) 400 (VCEO)
Note: The minimum current value is measured at 10°C min.

Characteristics

Input Module

Item G3TA-IAZR02S-US G3TA-IDZR02S-US G3TA-IDZR02SM-US
Operate time 20 ms max. 0.5 ms max.
Release time 20 ms max. 0.5 ms max.
Output ON voltage drop 1.6 V max. 1.6 V max.
Leakage current 5 μA max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance Malfunction: 1,000 m/s2
Ambient temperature Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards UL508 file No. E64562/CSA C22.2 (No. 0, No. 14) file No. LR35535
Weight Approx. 16 g

Output Module

Certified standards G3TA-OA202SZ-US G3TA-OA202SL-US G3TA-ODX02S-US G3TA-OD201S-US
Operate time 1/2 of load power source
cycle + 1 ms max.
1 ms max. 0.5 ms max. 2 ms max.
Release time 1/2 of load power source
cycle + 1 ms max.
2 ms max. 2 ms max.
Output ON
voltage drop
1.6 V rms max. 1.6 V max. 2.5 V max.
Leakage
current
5 mA max. (at 200 VAC) 1 mA max.
Insulation
resistance
100 MΩ min. (at 500 VDC)
Dielectric
strength
4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration
resistance
Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock
resistance
Malfunction: 1,000 m/s2
Ambient
temperature
Operating: -30°C to 80°C (with no icing or condensation)
Storage: -30°C to 100°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards UL508 file No. E64562, CSA C22.2 (No. 14) file No. LR3553
Weight Approx. 23 g
With up to four G3TA SSRs mounted before G7T Relays, switching is possible at the rated load current for each Relay.
G3TA Specifications 12
With G3TA SSRs mounted before every other G7T Relays, switching is possible at the rated load current for each Relay.
G3TA Specifications 13

G3TA

G3TA Dimensions 2 G3TA_Dimensions

Connecting Sockets

For Input (NPN, - Common) P7TF-IS16

G3TA Dimensions 5 P7TF-IS16_Dimensions

For Output (NPN, + Common) P7TF-OS16

G3TA Dimensions 7 P7TF-OS16_Dimensions

For Output (PNP, + Common) P7TF-OS08

G3TA Dimensions 9 P7TF-OS08_Dimensions

P7TF-O5

G3TA Dimensions 11 P7TF-O5_Dimensions